SAIDI and SAIFI

SAIDI and SAIFI are the standard measures of electricity network reliability. SAIDI (System Average Interruption Duration Index) is the average total minutes of interruption per customer over a period; SAIFI (System Average Interruption Frequency Index) is the average number of interruptions per customer.

What are SAIDI and SAIFI?

SAIDI and SAIFI are the two most widely used measures of how reliable an electricity network is. They are used by distributors and regulators in New Zealand, Australia and internationally.

  • SAIDI (System Average Interruption Duration Index) is the average total time, in minutes, that each customer on the network was without power over a period, usually a year.
  • SAIFI (System Average Interruption Frequency Index) is the average number of interruptions each customer experienced over the same period.

Together they show both how often customers lose power and how long they are off for.

How they are calculated

The calculations are simple in principle:

  • SAIDI = total customer minutes interrupted / total customers served
  • SAIFI = total customer interruptions / total customers served

For example, if a network serves 100,000 customers and an outage cuts power to 2,000 customers for 90 minutes, that event adds 180,000 customer minutes. Divided across the whole customer base, it adds 1.8 minutes to SAIDI and 0.02 to SAIFI.

A related measure, CAIDI (Customer Average Interruption Duration Index), is SAIDI divided by SAIFI. It shows the average length of an interruption for customers who had one.

Most networks only count sustained interruptions above a minimum length in these figures, with very short interruptions (momentary interruptions) tracked separately. The threshold depends on the reporting rules that apply.

Planned, unplanned and major events

Reliability is usually reported separately for planned and unplanned outages, because they mean different things. Planned SAIDI reflects how much scheduled maintenance and upgrade work a network is doing; unplanned SAIDI reflects the resilience of its assets and how quickly it restores faults.

Major storms can produce a single day with more outage minutes than the rest of the year combined. Regulators commonly use methods to identify and normalise these major events, so one extreme storm doesn’t distort the measure of underlying performance. The exact method depends on the regulatory regime.

How SAIDI and SAIFI are used

  • Regulation. In New Zealand, the Commerce Commission uses reliability measures in the quality standards it sets for regulated electricity distribution businesses. In Australia, the Australian Energy Regulator uses them in service performance incentives for DNSPs. The detail of the targets and incentives varies by network and regulatory period.
  • Asset management. Networks use SAIDI and SAIFI by feeder or area to decide where to invest in vegetation management, automation or undergrounding.
  • Public reporting. Reliability figures are disclosed so customers and stakeholders can see how networks perform over time.

Where the contact centre fits

The raw data for SAIDI and SAIFI comes from outage records in the outage management system: when each interruption started, when supply was restored and how many customers were affected.

The contact centre influences those numbers in practical ways. On low-voltage parts of the network, a customer call to the fault line may be the first sign of a fault. Fast answering, accurate location details and good fault triage help the control room find faults sooner and send field crews to the right place, which shortens outages. Accurate logging of when customers reported loss of supply also supports accurate reliability reporting.

How Telnet Helps

Where Telnet comes in

The contact centre doesn’t restore power, but it does affect how quickly faults are found and fixed. Telnet’s role is to make sure every fault report reaches your control room fast and accurately:

  • Accurate fault logging, 24/7. Our agents are trained in utility operations and log, triage and dispatch fault jobs to your field teams with visibility of outage status, job queues and crew availability.
  • No lost reports in a storm. Tulip answers on the first ring at any volume and logs fault reports straight into your systems, while shared agents move onto your lines within minutes.
  • Insight from every call. Fern analyses 100% of calls and emails, so you can see fault themes and recurring customer concerns by area.

We are the contact centre partner to more than half of New Zealand’s electricity networks.

FAQ

SAIDI and SAIFI FAQs

What's a good SAIDI figure?

There isn’t a single benchmark, because SAIDI depends heavily on the network. Dense urban networks with underground cables usually have far lower SAIDI than long rural networks with overhead lines exposed to storms and trees. Regulators typically compare a network against its own historical performance and targets rather than against other networks directly.

What is CAIDI?

CAIDI, the Customer Average Interruption Duration Index, is the average length of an interruption for customers who experienced one. It equals SAIDI divided by SAIFI. Where SAIDI and SAIFI describe the whole customer base, CAIDI shows how long restoration typically takes once an outage happens.

How does the contact centre affect SAIDI?

Indirectly. On parts of the network that aren’t remotely monitored, customer calls are often how a fault is first detected. If calls go unanswered or details are captured poorly, the fault may be found later or crews sent to the wrong place, extending the outage and adding customer minutes to SAIDI.

Ready to scale?

Outsourced contact centre
for New Zealand & Australia.

30+ years. 100% onshore. The leading provider to the energy & utilities industry.

Get in Touch